Product features
Product features
Comply with communication, medical safety certification
2 MOPP isolation protection
Leakage current ≤ 100μA
DOE Efficiercy Level VI
CoC V5 Tier2(2016)
Standby power consumption ≤0.075W
6.1V to 52V output, up to 24W
Working sea dial height 5000 meters
With a variety of interchangeable AC pins
Input Characteristics
Input voltage 80-264VAC
The frequency range is 47-63Hz
Input current 0.5A, 90VAC input condition
Surge current 70A Max at 240VAC input and cold start conditions
Contact current ≤ 100 μa at 264VAC input
The environment in general
Working temperature of 0 ~ 45 ℃ overall dimensions (length) 90.5 x33.5 (wide) x58.5 (high) mm
Storage temperature - 20 ~ 60 ℃ in weight 170 g
Working humidity 10 ~ 90% RH, noncondensable MTBF & gt; 100,000 HRS MIL-HDBK-217 at 25 ° C ambient temperature.
Storage humidity 5 ~ 90% RH isolation compression strength 4000 VDC input to the output
The working altitude is 5000m
Safety Approval
Safety/organization Medical I.T.E
CB IEC60601-1/IEC60601-1-11 IEC62368-1
UL ANSI/AAMI ES60601-1/60601-1-11 -
CAN/CSA-C22.2 NO. 60601-1
TüV Rheinland/Mark EN60601-1/EN60601-1-11 -
TüV Rheinland/GS - EN62368-1
CE - EN62368
CCC - GB4943.1
PSE - J62368
KC - K60950-1
RCM - AS/NES62368
Models & Parameters
Model | voltage | electric current | Rated power | Ripple and noise | Voltage tolerance | Linearity and load | Average efficiency | Start delay time |
(V) | (A) | (maximun) | Adjustment rate | |||||
UES24LCP1-XXXYYYSPA | 6.1-7.0 | 0.01-3.00 | 21W | 120mVpk-pk | ±5% | Linear adjustment rate: ±1% Load adjustment rate: ±5% | 86.20% | ≤3s |
7.1-8.0 | 0.01-2.62 | 21W | 120mVpk-pk | ±5% | 86.20% | ≤3s | ||
8.1-9.0 | 0.01-2.33 | 21W | 150mVpk-pk | ±5% | 86.20% | ≤3s | ||
9.1-10.0 | 0.01-2.10 | 21W | 150mVpk-pk | ±5% | 86.20% | ≤3s | ||
10.1-11.0 | 0.01-2.18 | 24W | 150mVpk-pk | ±5% | 87.00% | ≤3s | ||
11.1-12.0 | 0.01-2.00 | 24W | 150mVpk-pk | ±5% | 87.00% | ≤3s | ||
12.1-13.0 | 0.01-1.84 | 24W | 200mVpk-pk | ±5% | 87.00% | ≤3s | ||
13.1-14.0 | 0.01-1.71 | 24W | 200mVpk-pk | ±5% | 87.00% | ≤3s | ||
14.1-15.0 | 0.01-1.60 | 24W | 200mVpk-pk | ±5% | 87.00% | ≤3s | ||
15.1-16.0 | 0.01-1.50 | 24W | 200mVpk-pk | ±5% | 87.00% | ≤3s | ||
16.1-17.0 | 0.01-1.41 | 24W | 200mVpk-pk | ±5% | 87.00% | ≤3s | ||
17.1-18.0 | 0.01-1.33 | 24W | 200mVpk-pk | ±5% | 87.00% | ≤3s | ||
18.1-19.0 | 0.01-1.26 | 24W | 200mVpk-pk | ±5% | 87.00% | ≤3s | ||
19.1-20.0 | 0.01-1.20 | 24W | 240mVpk-pk | ±5% | 87.00% | ≤3s | ||
20.1-21.0 | 0.01-1.14 | 24W | 240mVpk-pk | ±5% | 87.00% | ≤3s | ||
21.1-22.0 | 0.01-1.09 | 24W | 240mVpk-pk | ±5% | 87.00% | ≤3s | ||
22.0-23.0 | 0.01-1.04 | 24W | 240mVpk-pk | ±5% | 87.00% | ≤3s | ||
23.1-24.0 | 0.01-1.00 | 24W | 240mVpk-pk | ±5% | 87.00% | ≤3s | ||
45.1-46.0 | 0.01-0.52 | 24W | 300mVpk-pk | ±5% | 87.00% | ≤3s | ||
46.1-47.0 | 0.01-0.50 | 24W | 300mVpk-pk | ±5% | 87.00% | ≤3s | ||
47.1-48.0 | 0.01-0.49 | 24W | 300mVpk-pk | ±5% | 87.00% | ≤3s | ||
48.1-49.0 | 0.01-0.48 | 24W | 300mVpk-pk | ±5% | 87.00% | ≤3s | ||
49.1-50.0 | 0.01-0.47 | 24W | 300mVpk-pk | ±5% | 87.00% | ≤3s | ||
50.1-51.0 | 0.01-0.46 | 24W | 300mVpk-pk | ±5% | 87.00% | ≤3s | ||
51.1-52.0 | 0.01-0.51 | 24W | 300mVpk-pk | ±5% | 87.00% | ≤3s |